The multi-circuit split-core panelboard system provides a solution for electrical load management and is ideal for retro-fit applications for dynamic loads.
The multi-circuit split-core panelboard system provides a solution for electrical load management and is ideal for retro-fit applications for dynamic loads.
The multi-circuit split-core panelboard system provides a solution for electrical load management and is ideal for retro-fit applications for dynamic loads.
Features
Applications
Input Power | 90 to 277 VAC, 50/60 Hz |
Power/Energy | IEC 62053-21 Class 1, ANSI C12.1-2008 |
Voltage | ±0.5% of reading 90 to 277 V line-to-neutral |
Sampling Frequency | 2,560 Hz |
Update Rate | 1.8 seconds |
Overload Capability | 22 kAIC |
Type | Modbus RTU |
Connection | DIP switch-selectable: 2-wire or 4-wire, RS-485 |
Address | DIP switch-selectable address: 1 to 247 (pairs of 2) |
Baud Rate | DIP switch-selectable: 9600, 19200, 38400 |
Parity | DIP switch-selectable: NONE, ODD, EVEN |
Communication Format | 8 data-bits, 1 start-bit, 1 stop-bit |
Operating Temperature | 32 to 140°F (0 to 60°C) <95% RH non-condensing |
Storage Temperature | -40 to 158°F (-40 to 70°C) |
Input Power | 90 to 277 VAC, 50/60 Hz |
Power/Energy | IEC 62053-21 Class 1, ANSI C12.1-2008 |
Voltage | ±0.5% of reading 90 to 277 V line-to-neutral |
Sampling Frequency | 2,560 Hz |
Update Rate | 1.8 seconds |
Overload Capability | 22 kAIC |
Type | Modbus RTU |
Connection | DIP switch-selectable: 2-wire or 4-wire, RS-485 |
Address | DIP switch-selectable address: 1 to 247 (pairs of 2) |
Baud Rate | DIP switch-selectable: 9600, 19200, 38400 |
Parity | DIP switch-selectable: NONE, ODD, EVEN |
Communication Format | 8 data-bits, 1 start-bit, 1 stop-bit |
Operating Temperature | 32 to 140°F (0 to 60°C) <95% RH non-condensing |
Storage Temperature | -40 to 158°F (-40 to 70°C) |